7.6.2 - Agricultural installations
                    Of paramount importance where livestock 
                      are present is the indication that the levels of separated 
                      extra-low voltage (SELV) are too high. Whilst the Regulations 
                      do not suggest a safe voltage for animals, simply suggesting 
                      a level 'appropriate to the type of livestock', a practical 
                      value is likely to be no higher than 25 V. Such systems, 
                      as well as those complying with SELV requirements, must 
                      be protected to IP44 (ie, protected from solid objects not 
                      exceeding 1 mm and from splashing water) or the insulation 
                      must be able to withstand 500 V r.m.s. for one minute.
                    All socket outlets must be protected by 
                      residual current device(s) (RCDs) with an operating current 
                      of no more than 30 mA. Whilst it is accepted that livestock 
                      cannot be protected by earthed equipotential bonding and 
                      automatic disconnection (sometimes known as EEBAD) because 
                      the voltages to which they would he subjected in the event 
                      of a fault are unsafe for them, changes to standard installation 
                      requirements do offer some additional protection. The requirements 
                      are:
                    1. - Disconnection times for the 
                      operation of protective devices are reduced, usually to 
                      half the normal value. The maximum times are voltage related, 
                      and are shown in {Table 7.3}.
                    
                       
                        | Table 7.3 - Maximum 
                          disconnection times for agricultural circuits for ----------------- livestock (TN systems)
 | 
                       
                        |  | Supply voltage (Uo) | Disconnection time | 
                       
                        |  | (volts) | (seconds) | 
                       
                        |  | 120 | 0.35 | 
                       
                        |  | 220 to 277 | 0.20 | 
                       
                        |  | 400 and 480 | 0.05 | 
                    
                    The application of these reduced connection 
                      times leads to the reduced levels of maximum 
                      earth-fault loop impedance, shown in {Table 
                      7.4} for 240 
                      V circuits.
                    2. 
                      - Fixed equipment and distribution circuits are permitted 
                      to have a disconnection time of 5 s, which is the same as 
                      for normal installations, and require the maximum earth-fault 
                      loop impedance values shown in {Tables 
                      5.2 and 
                      5.4}. An exception is where the fixed equipment is fed 
                      from the same distribution board as circuits requiring disconnection 
                      in 0.2 s at 240 V. In such a case Either the resistance 
                      of the main protective conductor from the distribution board 
                      to the point of connection to the main equipotential bonding 
                      system must be low enough to ensure that its volt drop when 
                      fault current flows does not exceed 25 V, 
                    or the distribution board must have its 
                      exposed conductive parts bonded to all extraneous conductive 
                      parts (such as water pipes) in the area.
                    3. - The maximum of 25 V for the 
                      potential difference across the protective conductor under 
                      fault conditions stated above is applied to all final circuits. 
                      This is half of the level accepted in other installations, 
                      so the protective conductor resistance must have half the 
                      normal value. Note that where an IT system (usually a generating 
                      plant) is used, special requirements apply - these are outside 
                      the scope of this Guide, and advice must be sought from 
                      a qualified electrical engineer.
                    4. - Supplementary equipotential 
                      bonding must be applied to connect together all exposed 
                      and extraneous conductive parts which are accessible to 
                      livestock and the main protective system. It is recommended 
                      that a metallic grid should be laid in the floor and connected 
                      to the protective conductor.
                    5. - Where an RCD is used it is 
                      important to ensure that the earth electrode resistance 
                      is not so high that the 25 V level will be exceeded before 
                      operation. This can be verified by using the expression
                    
                    where RA = the combined earth 
                      electrode and protective conductor resistance, 
                      and An = the rated residual operating current of the RCD.
                      
                      
                    Application of the expression gives 833 
                      Ohms for a 30 mA device, 250 Ohms for a 100 mA, 83 ohms 
                      for a 300 mA and 50 Ohms for a 500 mA. Values higher than 
                      200 Ohms should not be used or there may be instability. 
                      The resistance of the protective conductors is usually negligible 
                      compared with that of the earth electrode.
                    The equipotential bonding required will 
                      create an earth zone, and special measures are necessary 
                      where a circuit fed from this zone extends outside it. If 
                      the equipment could be touched by a person in contact with 
                      the general mass of earth, disconnection time must not exceed 
                      0.2 s, even for fixed equipment. This means that {Table 
                      7.4} 
                      will apply to such circuits.
                    Fire is a particular hazard in agricultural 
                      premises where there may be large quantities of loose straw 
                      or other flammable material. A particular fire hazard on 
                      agricultural premises is damage to the wiring by rodents 
                      gnawing at cables. This effect can be reduced by cable runs 
                      which are below ceilings rather than in roof spaces and 
                      by the use of steel conduits. The Regulations require the 
                      protection of the system by an RCD with an operating current 
                      not greater than 500 mA. In practice, a 300 mA rating is 
                      likely to be used. This will result in problems of discrimination 
                      between this unit and those of lower operating current rating 
                      unless the main RCD is of the time delayed type (see 
                      {5.9.3}). Care must be taken to ensure that heaters 
                      are not in positions where they will ignite their surroundings; 
                      a clearance of at least 500 mm is required for radiant heaters.
                    All electrical equipment must be protected 
                      to IP44, and chosen to be suitable to operate under the 
                      onerous conditions they will experience. Wiring must be 
                      inaccessible to livestock and must be vermin proof. In practice, 
                      this will probably mean enclosure in galvanised steel conduit, 
                      or the use of mineral insulated cables, Switch and control 
                      gear must be to IP44 and constructed of, or enclosed in, 
                      insulating material. Switches for emergency use must not 
                      be in positions accessible to cattle, or where cattle may 
                      make operation difficult. Emergency switches should 
                      disconnect all live conductors including the neutral. It 
                      may be necessary to omit isolators in some cases to ensure 
                      that essential supplies (such as broiler house fans) are 
                      not disconnected unintentionally. The likelihood of panic 
                      amongst animals when emergencies occur must be taken into 
                      account.
                    
                       
                        | Table 7.4 - Maximum 
                          earth-fault loop impedance values for 240 V agricultural 
                          circuits to give a maximum 0.2 s disconnection time | 
                       
                        | Type of protection | Protection rating | Max. loop impedance | 
                       
                        |  | (A) | (ohms) | 
                       
                        | Cart. Fuse, BS 1361 | 5 | 9.60 | 
                       
                        |  | 15 | 3.00 | 
                       
                        |  | 20 | 1.55 | 
                       
                        |  | 30 | 1.00 | 
                       
                        | Cart. Fuse BS 88 pt 2 | 6 | 7.74 | 
                       
                        |  | 10 | 4.71 | 
                       
                        |  | 16 | 2.53 | 
                       
                        |  | 20 | 1.60 | 
                       
                        |  | 25 | 1.33 | 
                       
                        |  | 32 | 0.92 | 
                       
                        | MCB type 1 | 5 | 12.00 | 
                       
                        |  | 10 | 6.00 | 
                       
                        |  | 15 | 4.00 | 
                       
                        |  | 20 | 3.00 | 
                       
                        |  | 30 | 2.00 | 
                       
                        | MCB type 2 | 5 | 6.86 | 
                       
                        |  | 10 | 3.43 | 
                       
                        |  | 15 | 2.29 | 
                       
                        |  | 20 | 1.71 | 
                       
                        |  | 30 | 1.14 | 
                       
                        | MCB type 3 | 5 | 4.80 | 
                       
                        |  | 10 | 2.40 | 
                       
                        |  | 15 | 1.60 | 
                       
                        |  | 20 | 1.20 | 
                       
                        |  | 30 | 0.80 |