Table 6.2 - Allowance for diversity

Note the following abbreviations :
X is the full load current of the largest appliance or circuit
Y is the full load current of the second largest appliance or circuit
Z is the full load current of the remaining appliances or circuits

Type of final circuit   Type of premises  
  Households Small shops, stores, offices Hotels, guest houses
Lighting 66% total demand 90% total demand 75% total demand
Heating and power 100% up to 10 A + 50% balance 100%X + 75%(Y+Z) 100%X + 80%Y + 60%Z
Cookers 10 A + 30% balance + 5 A for socket 100%X + 80%Y + 60%Z 100%X + 80%Y + 60%Z
Motors (but not lifts)   100%X + 80%Y + 60%Z 100%X + 50%(Y+Z)
Instantaneous water heaters 100%X + 100%Y + 25%Z 100%X + 100%Y + 25%Z 100%X + 100%Y + 25%Z
Thermostatic water heaters 100% 100% 100%
Floor warming installations 100% 100% 100%
Thermal storage heating 100% 100% 100%
Standard circuits 100%X + 40%(Y+Z) 100%X + 50%(Y+Z) 100%X + 50%(Y+Z)
Sockets and stationary equip. 100%X + 40%(Y+Z) 100%X + 75%(Y+Z) 100%X + 75%Y + 40%Z