 32 AMP Shown
MCB terminal capacity, 25 mm on all mcb's |
Hager MCB ( Type C ) Rated 40 Amps | | Type C devices are capable of supplying the majority of inductive and capacitive loads such as motors, transformers and tungsten or fluorescent lighting. | Surges on energisation, for example with discharge lighting, may well reach 25 times the rated current of the device, but only for very short duration. Type B devices will often be adequate, but for more specialised circuits, a Type C may be required. The lighting fitting manufacturers recommendations should be observed. |
|