TLC Electrical Logo

63 Amp Hager MCB C Type - Motor Rated

  part of  Hager  MCB's - Type B & C
Main Index   •   Technical   •   View Your Order / Checkout   •   Quick Order Entry   •   Stock Availablity   •   Delivery
63 Amp Hager MCB C Type - Motor Rated NC163  
63 Amp Hager MCB C Type - Motor Rated

MCB terminal capacity,

25 mm on all mcb's

Hager MCB ( Type C )
Rated 63 Amps
Type C devices are capable of supplying the majority of inductive and capacitive loads such as motors, transformers and tungsten or fluorescent lighting.Surges on energisation, for example with discharge lighting, may well reach 25 times the rated current of the device, but only for very short duration. Type B devices will often be adequate, but for more specialised circuits, a Type C may be required. The lighting fitting manufacturer’s recommendations should be observed.
Commercial Consumer Unit use

Hager MCB's detect overcurrents due to both overload and fault currents.
The MCB will operate and interrupt the supply to prevent damage to the installation.

  • Hager commercial MCBs have a short circuit breaking capacity of 10000A (M10).
  • The current carrying capacity of the cable should always exceed the current rating of the MCB to prevent damage.
  • The operating dolly may be locked in either the ON or OFF position without affecting the ability of the trip mechanism to operate.
  • When the green flag below the dolly is visible, then a contact gap of 4 mm has been achieved. Hager MCBs may therefore be used as single pole isolating switches where appropriate.
Technical: MCB Selection 
Order Code Description Price (ex vat) Qty    
HG NC16363 Amp Hager MCB C Type - Motor Rated
EA
6.50
graphic
Top of Page Metric Imperial Converter Proceed to Checkout

Copyright © 2002-2008 TLC (Southern) Ltd - Company Information - Terms and Conditions - Customer Services - Help - Privacy - Contact TLC
www.tlc-direct.co.uk