- SUPPLY
Voltage: 110V/240V ±10% 50/60Hz Power Consumption: 10/220V A (excluding run) - EARTH CONTINUITY TEST (8A)
Test Voltage: 6V a.c. nominal with no load Test Current: 8A a.c. nom @ 0.1O. 5A a.c. nom@0.5O Range: 0-1.99O Accuracy: ±10% of reading ±2 digits - EARTH CONTINUITY TEST (25A)
Test Voltage: 6V a.c. nominal with no load Test Current: 25A a.c. nom @ 0.1O. 10A a.c. nom @ 0.5O Range: 0-1.99O Accuracy: ±10% of reading ±2 digits - EARTH SCREEN TEST (100mA)
Test Voltage: 130mV d.c. nominal open circuit Test Current: 100mA d.c. nominal constant current Range: 0-1.99O Accuracy: ±10% of reading ±1 digit - INSULATION TEST
Test Voltage: 500V d.c., -0%, +20%, at 2MO and 7MO Short Circuit Current: 1mA d.c. nominal Display Range: 0-19.9MO Accuracy of Indication: ±5% of reading ±1 digit - RUN CURRENT TEST
Range: 0-19.9A Accuracy: ±10% of reading ±1 digit - EARTH LEAKAGE TEST
Range: 0 - 19.9mA Accuracy: ±10% of reading ±1 digit
| - FLASH TEST
Test Voltage: 1.5kV a.c. - Class I. 3.0kV a.c. - Class II Display Range:0-19.9mA a.c. Usable Range:0-3mA a.c. (current trip @ 4mA nominal) (short circuit current 5mA nominal) Accuracy: ±5% of reading ±1 digit - LEADS
Mains: 1.5 metre fixed lead with a 13A moulded plug. Earth Continuity: 1.5 metre long, detachable lead with a heavy duty, shrouded crocodile clip. Flash Gun: A safety gun, giving extra user protection for flash testing. Compatible with the EasyPAT and MicroPAT. 4mm socket. 110/240V Adaptor: 110V 16A plug (BS4343) to 240V 13A free socket (BS1363) - SOCKETS
Mains: 240V 13A to BS1363. 110V 16A to BS4343. Flash: 4mm high voltage safety socket - LAMPS
Flash: Neon lamp which illuminates when flash test is active. Over Temperature: Red LED which illuminates when the temperature limit of the instrument is exceeded. - FUSES
Front Panel: 16A (FF), 1.25, HBC, ceramic Plug: 13A, 1, HBC, ceramic Internal: 3.15A (F), 5 x 20mm, HBC, ceramic - DISPLAY
LCD: 0.7" high, 2½ digit LCD with annunciations to indicates supply voltage of the mains and units of measurement in use. - TEMPERATURE
Operating: 0° to +35°C Storage: -10° to +50°C
|