40 Amp 30mA RCD 4 Pole - Wylex WRS40/4  
40 Amp 30mA RCD 4 Pole - Wylex

RCD terminal capacity,
25 mm


Usage,

Selective 3 Phase Circuits
within an Enclosure


Four Module

Wylex 4 pole RCD

40 Amp 30mA
40 Amp 30mA

RCD's Residual Current Device Offers Protection against Electric Shock


  • Wylex 4 pole RCDs may be used to provide earth fault protection on 3 phase, 3 wire systems, as the current balance mechanism does not require a neutral to be connected in order to operate effectively.
  • Wylex RCDs must never be used as the sole method of direct contact protection, but are invaluable in providing supplementary protection in high risk environments where damage may occur.
  • However Wylex 4 pole RCDs do, ideally, require a neutral conductor to be provided on the supply side of the RCD in order to ensure that the test circuit operates satisfactorily.
  • Where connection of a neutral supply is not possible, then an alternative method of ensuring that the test button is operational is to fit a suitably rated resistor between the load side neutral pole and a phase pole not associated with the normal test button operation.
Technical: RCD Selection and Info and Data Sheets 
Order Code Description Price (ex vat) Qty    
WY WRS40/440 Amp 30mA RCD 4 Pole - Wylex
EA
40.50