After installation switch on mains
electricity to all units, and check the following:-
|
1.
|
Check that the
green mains indicator LED is on and the pendant light (room
light) is operational with the light switch.
|
2.
|
If the green
LED is off or the pendant light stays on, check breakers, fuses,
wiring etc. Also check installation of transit switches. |
3. |
Check red LED
flashes approximately every 40 secs.
|
4. |
Press the test
button for up to 10 secs. to ensure the sensor chamber, electronics,
sounder and the room light stays on (turns on even if light
is turned off).
The red LED should flash while the horn is
sounding. |
5.
|
Release button
and the alarm will stop. Room light will operate normally and
unit resumes standby condition.
|
|
6. |
Test interconnected
alarms (if applicable) by pressing any test button. All alarms
should activate and room lights turn on within 5 secs. of the
first horn sounding. Red LED on first unit only will flash approx.
once a second. Check all other units similarly.
|
7.
|
To test the emergency
light. Turn off mains power at the distribution board and check
that the green LED is extinguished. In daylight, cover dusk/dawn
sensor on the unit with palm of hand and the emergency lights
will operate. After a few minutes, restore mains supply at distribution
board and the emergency light will turn off and green LED will
illuminate. |