             Technical 
              Index - Photain Index 
                    
                  
                     
                      
                     
                     
                      |   | 
                        | 
                     
                     
                      
                     
                     
                      |   | 
                        | 
                     
                     
                      
                     
                     
                      | * Low Profile Aesthetic Design | 
                      * Optical chamber using Tyndall principle | 
                     
                     
                      | * Surface Mounted high reliability technology | 
                      * LED Alarm Indication | 
                     
                     
                      | * Integral Locking Facility | 
                      * Remote indicator connection | 
                     
                     
                      | * Advance immunity against insect ingress | 
                      * Surface and Recess Base Mounting | 
                     
                     
                      |  
                           
                        This unit operates on the light scattering principle. 
                          An internal infra red light source is pulsed, with the 
                          light beam arranged so as to by-pass a receiving unit. 
                          The presence of smoke scatters the light beam, causing 
                          it to be reflected onto the receiving photocell. An 
                          evaluation circuit measures the amount of light and 
                          compares it to a reference. The detector is triggered 
                          into an alarm state when the amount of smoke exceeds 
                          a preset level. To ensure against false alarms, several 
                          pulse readings are taken and compared before the detector 
                          is triggered into alarm. 
                          
                       | 
                     
                   
                  
                     
                      
                     
                     
                      Detector type: 
                        Visible smoke detection 
                         
                        Detection principle: 
                        Photoelectric detection of light scattered in a forward 
                        direction by smoke particules 
                         
                        Chamber configuration: 
                        Axially disposed light source lens systems and light sensor 
                         
                        Emitter: 
                        GaA1As diode 
                         
                        Sensor: 
                        Silicon photodiode 
                         
                        Sampling frequency: 
                        Once every 5 seconds nominal 
                         
                        Confirmation frequency: 
                        1 second 
                         
                        Number of confirmation: 
                        2 | 
                      Supply voltage: 
                        15 - 30vDC 
                         
                        Quiescent current: 
                        Less than 60 microAmps 
                         
                        Alarm current: 
                        Max 100mA 
                         
                        Alarm indicator: 
                        Red light emitting diode illuminated 
                        continuously 
                         
                        Remote alarm output: 
                        Rated at 50mA max. 
                         
                        Sensitivity: 
                        Responds to all types of fire tests as per EN54 Part7 
                         
                        Operating temperature range: 
                        -10 to +75°C 
                         
                        Humidity: 
                        Up to 95% R.H. 
                         
                        Wind: 
                        Insensitive to wind interference 
                         
                        Altitude: 
                        0-6000 metres | 
                      Vibration: 
                        To EN54, Part 7, annex L 
                         
                        Impact: 
                        To EN54, Part 7, annex O 
                         
                        Shock: 
                        To EN54, Part 7, annex N 
                         
                        Electrical transients: 
                        500v spikes rise time 2 microseconds 
                         
                        Weight: 
                        Detector: 119grammes 
                        Base: 75grammes 
                         
                        Dimensions: 
                        Detector in Base Assembly 
                        Height: 60mm 
                        Diameter: 108mm 
                         
                        Colour: 
                        White 
                         
                        Environmental Protection 
                        IP32 
                         
                        Technical compliance: 
                        This detector is approved to EN54-7, BS5445 Part 7 | 
                     
                     
                      |   | 
                        | 
                        | 
                     
                     
                      |   | 
                        | 
                        | 
                     
                   
                    
                   |