16 zone addressable fire alarm panel supplied with 1 loop. Expandable to 2 loops using MAGPRO16-L250. A maximum of 250 devices can be connected to each loop.
16 Zones.
Maximum 250 devices per loop.
Memory Log: 10,000 events.
Networkable up to 32 Panels.
4 x 40 character LCD display.
Micro USB port for PC connection.
Loop & battery calculator software included.
Certified to EN542/4.
CPR Compliant.
Inputs Loops: 1 expandable to 2 Devices Per Loop: 250 Protocol: MAGPRO
Power Mains Fail Consumption: 125mA DC 1 Loop 213mA DC 2 LOOP Mains Supply: 230V AC + - 10% Max Loop Current: 500mA DC Backup: 1x12V 17Ah
Outputs 2 Sounders: 24v DC @ 500mA 4 Programmable Relays: 24v DC @ 100mA 3 Monitored Outputs: 24v DC @ 100mA 3 Monitored Inputs: Volt free contacts
Environment Working Temperature: -5C TO +40C Storage: -10C TO 60C Humidity: 0 - 95%.