                   CCSR Self Regulating 
                    Frost Protection Heat Tapes 
                   
                    SELECTION 
                      Use table 1 to select the correct product. In most instances 
                      the cable can be applied in a straight line along the length 
                      of the pipe but if an even spiralling is required, this 
                      is indicated. The table is based on pipe freeze protection 
                      against -20°C. 
                    Table1 
                    
                       
                       
                        Pipe 
                          Diam. 
                          (mm)  | 
                        Insulation Thickness (mm) | 
                       
                       
                        | 12 | 
                        25 | 
                        50 | 
                       
                       
                        | 12 | 
                        CCSR-10 
                          Straight  | 
                        CCSR-10 
                          Straight  | 
                        CCSR-10 
                          Straight  | 
                       
                       
                        | 25 | 
                        CCSR-15 
                          Straight  | 
                        CCSR-10 
                          Straight  | 
                        CCSR-10 
                          Straight  | 
                       
                       
                        | 50 | 
                        CCSR-24 
                          Straight  | 
                        CCSR-10 
                          Straight  | 
                        CCSR-10 
                          Straight  | 
                       
                       
                        | 75 | 
                        CCSR-24 
                          1.3m cable/1m pipe | 
                        CCSR-24 
                          Straight  | 
                        CCSR-10 
                          Straight  | 
                       
                       
                        | 100 | 
                        CCSR-24 
                          1.8m cable/1m pipe | 
                        CCSR-24 
                          Straight  | 
                        CCSR-15 
                          Straight  | 
                       
                       
                        | 150 | 
                        CCSR-24 
                          3m cable/1m pipe | 
                        CCSR-24 
                          1.4m cable/1m pipe | 
                        CCSR-15 
                          1.2m cable/1m pipe | 
                       
                      
                     
                     
                       
                      Table 2 - Additional length for flanges, valves and supports (m) 
                    
                       
                       
                        | Pipe Diam. (mm) | 
                        Pair of Flanges | 
                        Valve | 
                        Support | 
                       
                       
                        | 12 | 
                        0.23 | 
                        0.10 | 
                        0.10 | 
                       
                       
                        | 25 | 
                        0.28 | 
                        0.15 | 
                        0.10 | 
                       
                       
                        | 50 | 
                        0.30 | 
                        0.30 | 
                        0.15 | 
                       
                       
                        | 75 | 
                        0.45 | 
                        0.40 | 
                        0.15 | 
                       
                       
                        | 100 | 
                        0.60 | 
                        0.50 | 
                        0.20 | 
                       
                       
                        | 150 | 
                        0.80 | 
                        0.60 | 
                        0.25 | 
                       
                      
                     
                    Example: To frost protect a 75mm diameter pipe 10 
                      metres long. To be fully insulated with 25mm thick insulation. 
                      The pipe has 10 supports and the lowest temperature is –20ºC. 
                   
                   
                    1) From the Table 1 cross reference 75mm diameter 
                      and 25mm insulation. Select CCSR-24 installed straight 
                      along the pipe. 
                      2) Length of cable required is 10m (as cable to be installed 
                      straight along the pipe). 
                      3) Add extra length for the support (Table 2) 10 x 0.15 
                      = 1.5m. 
                      4) Total length of cable = 10 + 1.5 = 11.5m of CCSR-24 
                      + 1 CCSR-T 1 termination kit. 
                   
                  
                  
                     
                     
                      | Ref No | 
                      Maximum Output 
                        W/M@10°C  | 
                      Length | 
                      Voltage | 
                      Maximum Exposure Temperature (Intermittent) | 
                      Minimum Installation Temperature | 
                      Maximum Circuit Length | 
                     
                     
                      | CCSR-10 -CL | 
                      10 | 
                      By the metre | 
                      230 | 
                      66 °C | 
                      -20 °C | 
                      164m | 
                     
                     
                      | CCSR-10 | 
                      10 | 
                      75m dispensing box | 
                      230 | 
                      66 °C | 
                      -20 °C | 
                      164m | 
                     
                     
                      | CCSR-15-CL | 
                      15 | 
                      By the metre | 
                      230 | 
                      66 °C | 
                      -20 °C | 
                      140m | 
                     
                     
                      | CCSR-15 | 
                      15 | 
                      75m dispensing box | 
                      230 | 
                      66 °C | 
                      -20 °C | 
                      140m | 
                     
                     
                      | CCSR-24-CL | 
                      24 | 
                      By the metre | 
                      230 | 
                      66 °C | 
                      -20 °C | 
                      106m | 
                     
                     
                      | CCSR-24 | 
                      24 | 
                      75m dispensing box | 
                      230 | 
                      66 °C | 
                      -20 °C | 
                      106m | 
                     
                    
                   
                  Termination and splice/tee kits available. 
                    For overriding control, internal and external mounting air 
                    thermostats available (FST-IN and FST-EX). 
                   |