2.5 - Low voltage generating sets
                    A 
                      completely new Section of 24 Regulations was introduced 
                      by the 1997 amendments dealing with low voltage generating 
                      sets. This set of Regulations was numbered Section 551, 
                      the existing [551 - Transformers] being renumbered as 555 
                      to accommodate it.
                    Where 
                      low voltage or extra-low voltage generating sets are used 
                      to power an installation, (a) as the sole means of supply, 
                      or (b) as a backup in case of failure of the supply, or 
                      (c) for use in parallel with the supply, these Regulations 
                      apply. Self-contained systems, operating at extra-low voltage, 
                      which include the source of energy (usually batteries) as 
                      well as the load are not covered.
                    Generating 
                      sets, for the purpose of these Regulations, include not 
                      only rotating machines powered by combustion engines, turbines 
                      and electric motors, but also photovoltaic cells (which 
                      convert energy from light into electricity) and electrochemical 
                      accumulators or batteries. Protection of circuits fed from 
                      generators must be no less effective than those applying 
                      to mains-fed systems. Voltage and frequency variations are 
                      much more likely with generators than with a mains supply, 
                      and it must be ensured that they do not cause danger or 
                      damage t6 the equipment.
                    Protection 
                      of persons and of equipment must be at least as effective 
                      in the case of an installation fed permanently or occasionally 
                      by a generating set as for a mains-fed installation. Special 
                      requirements for bonding apply where static invertors are 
                      used. A static invertor is an electronic system which produces 
                      an ac supply at a given voltage, frequency and waveform 
                      from a dc source (often from a battery). When two or more 
                      generating sets operate in parallel, circulating harmonic 
                      currents are a possibility. Such currents are at frequencies 
                      which are multiples of the normal supply frequency, and 
                      will possibly result in overloading of the connecting cables 
                      unless steps are taken to reduce or remove them. When not 
                      intended to run in parallel with the mains supply, for example 
                      when used as a standby system. interlocks and switching 
                      must be provided to ensure that parallel operation is not 
                      possible.
                    When 
                      a generating set is intended as a standby system for use 
                      in place of the mains supply in the event of failure, precautions 
                      must be taken to ensure that the generator cannot operate 
                      in parallel with the mains. Methods include an interlock 
                      between the operating systems of the changeover switches, 
                      a system of locks with a single transferable key, a three-position 
                      break-before-make changeover switch, or an automatic changeover 
                      switch with an interlock.
                    Where 
                      generators are intended to operate in parallel with the 
                      mains supply, the Supply Company must be consulted to ensure 
                      that the generator is compatible in all respects (including 
                      power factor, voltage changes, harmonic distortion, unbalance, 
                      starting, synchronising and voltage fluctuation) with the 
                      mains supply. In the event of any of the above parameters 
                      becoming incompatible with the mains supply, the generating 
                      set must be automatically disconnected. Such disconnection 
                      must also occur if its voltage or frequency stray outside 
                      the limits of protection. It must be possible to isolate 
                      the generating set from the mains supply, and that means 
                      of isolation must always be accessible to the supply company.