7.14.2  - Garden installations
                    Increasing use is being made of electrical 
                      supplies in the garden, for pond pumping systems, lighting, 
                      power tools and so on. The following points apply:
                    1. - Socket outlets installed indoors 
                      but intended to provide outdoor supplies must be protected 
                      by an RCD with a maximum operating current of 30 mA. Any 
                      portable equipment not fed from a socket outlet must also 
                      be protected by an RCD with a 30 mA operating current. Outdoor 
                      sockets also require the same RCD protection and must also 
                      satisfy IP44 requirements (see 
                      {2.4.3}).
                    2. - Garden lighting, pond pumps 
                      and so on should preferably be of Class Ill construction, 
                      supplied from a SELV system and having a safety isolating 
                      transformer supply. Where 240 V equipment must be used, 
                      it should be Class II double insulated (no earth) and should 
                      be suitably protected against the ingress of dust or water. 
                      If accessible Class I equipment is used its supply system 
                      must have an earth fault loop impedance low enough to allow 
                      disconnection within 0.4 s in the event of an earth fault.
                    3. - Earthing must be given special 
                      attention. All buildings must be provided with 30 
                      mA RCD protection, but the Electricity Supply Company should 
                      be consulted to ascertain their special requirements if 
                      the supply system uses the PME (TN-C-S) system. Where the 
                      supplier does not provide an earth terminal, each outbuilding 
                      must be provided with an adjacent earth electrode.
                    4. - Outbuildings are often of light 
                      construction and therefore are subject to extremes as far 
                      as temperature swings are concerned. It is therefore important 
                      to bear this in mind when selecting equipment and components.
                    5. - Extraneous conductive parts 
                      of an outbuilding which may become live due to a fault should 
                      be bonded to the incoming protective conductor.
                    6. - Every outbuilding with an electrical 
                      supply should be provided with a means of isolation to disconnect 
                      all live conductors including the neutral.
                    7. - All outbuildings where protection 
                      against direct contact is by earthed equipotential bonding 
                      and automatic disconnection of the supply should have a 
                      disconnection time in the event of an earth fault which 
                      does not exceed 0.4 s.
                    8. - Cables which are not buried 
                      must be shielded from direct sunlight, whose ultraviolet 
                      content will affect plastics. Cables with ultra-violet protected 
                      sheaths may be used; the preferred colour for such cables 
                      is black.
                    9. - Large garden ponds present 
                      a particular problem because of the probability that sooner 
                      or later people will fall into them. In such a case, the 
                      Regulations applying to swimming pools (see 
                      {7.3}) should be applied. Pumps and lighting should 
                      be SELV with the safety source at least 3.5 m outside the 
                      edge of the pond. All cables in the pond must be in ducts 
                      or conduits which are built into it and not be allowed to 
                      lie loose. All pond equipment must be protected to IP55 
                      (see 
                      {2.4.3}) or better.